Table 8.2 rio scan times for adapters, Rio scan time calculation (t – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 133

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

Specifications A-5

RIO Scan Time Calculation (T

RIO

)

The RIO scan time is calculated by identifying the baud rate and
image size of each logical device on the RIO link. Locate the
corresponding time value in the following table. If you are using
multiple logical devices, add the time values together to determine the
total RIO scan time (T

RIO)

.

T

RIO

= T

adapter 1

+ T

adapter 2

+ T

adapter 3

Table 8.2 RIO Scan Times for Adapters

(1)

(1) The table shown above is based on PLC-5 processors. If another type of processor is used, refer to its user

manual for T

RIO

.

Adapter Size

Baud Rate

57.6K

115.2K

230.4K

1/4 logical rack

6.0ms

3.5ms

2.5ms

3/4 logical rack

7.5ms

4.5ms

3.0ms

Full logical rack

9.5ms

5.5ms

3.5ms

Advertising