A-2 Specifications

Network Specifications

Baud Rate Determination of Maximum Cable Length and Terminating
Resistor.

Throughput is the time between when a control system senses an
input event on an I/O module in a 1747-ASB chassis to when an
output event occurs on an I/O module within the same 1747-ASB
chassis. There are three types of 1747-ASB module throughput:

Troughput Production

discrete throughput (time from discretely mapped input to
discretely mapped output) without block transfers present

discrete throughput (time from discretely mapped input to
discretely mapped output) with block transfers present

block transfer throughput (time from block transfer mapped
input to block transfer mapped output)

Discrete Throughput Overview

The 1747-ASB module system discrete throughput is comprised of:

the total PLC or SLC processor scan time

the total RIO link scan time

1747-ASB module backplane scan time

the scanner module output delay time (only if scanner is a
separate module from the processor, otherwise value is 0)

the scanner module input delay time (only if scanner is a
separate module from the processor, otherwise value is 0)

the input module delay time

the output module delay time

Table 8.1 Baud Rate Determination of Maximum Cable Length and Terminating
Resistor Size

Baud Rate

Maximum Cable Distance
(Belden 9463)

Resistor Size

Using Extended
Node Capability

57.6K baud

3048 meters (10,000 feet)

82

1/2 Watt

115.2K baud

1524 meters (5,000 feet)

230.4K baud

762 meters (2,500 feet)

Not Using
Extended Node
Capability

57.6K baud

3048 meters (10,000 feet)

150

1/2 Watt

115.2K baud

1524 meters (5,000 feet)

230.4K baud

762 meters (2,500 feet)

82

1/2 Watt