I/O Runtime Fault Codes - Code 4
Code 4
(1)
Meaning
I/O Parity Error
Hardware Parity Error or module installed or removed under
power
I/O Module Removed Under Power
File Access Grant Timeout (specialty I/O only)
I/O Module Fault (generic)
I/O Module Reported Error Code
I/O Module Reported Error Code Unknown
Module Inserted Under Power
(1) The fault code is alternated with the corresponding slot number (L slot#).