Publication 1747-UM006B-EN-P - June 2003

Configuration 4-5

Baud Rate DIP Switch Settings

If the invalid switch setting is selected, a 1747-ASB module error
occurs.

Primary/Complementary Chassis (SW2-3)

SW2 switch 3 determines whether the 1747-ASB module appears to
the scanner as a primary or complementary chassis.

Primary/Complementary SLC Chassis DIP Switch Setting

If you are not using complementary I/O, all 1747-ASB modules
should be configured with SW2-3 in the default position. If a primary
chassis is configured and no complementary chassis exists, the
scanner wastes time trying to scan a complementary chassis that is not
there.

Complementary I/O allows two 1747-ASB modules to overlap their
input and output images, creating one image within the scanner, thus
maximizing image space. The combined image is located where the
primary image is configured to reside. Complementary I/O is very
useful when portions of your input and output images are unused.

SW2

57.6K

115.2K

230.4K

Invalid

SW2

SW2

SW2

4

1

23

5
6

7

8

O

N

4

1

23

5
6

7

8

O

N

4

1

23

5
6

7

8

O

N

4

1

23

5
6

7

8

O

N

SW2

Primary

4

1

23

5

6

7

8

O

N

SW2

Complementary (default)

4

1

23

5

6

7

8

O

N

4

1

2

3

456

7

8

SW1

S

W2

SW3

1

23

5
6

7

8

1
23

4
5
6

7

8

O

N

O

N

O

N

Specialty I/O Mode
I/O Module Keying

Addressing Mode

Last Chassis/PLC-3 Backup

Link Response

Processor Restart Lockout

Hold Last State

Baud Rate

Primary/Complementary Chassis

ASB Module Image Size

Logical Group Number

Logical Rack Number

ON

OFF

Reserved