Contacting rockwell automation – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 98

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

7-2 Troubleshooting

Contacting Rockwell
Automation

If you need to contact Rockwell Automation for assistance, please
have the following information available when you call:

Processor type, 1747-ASB series letter, and firmware (FRN)
number. See label on left side of processor and 1747-ASB
module.

LED status and error codes

hardware types in the system including I/O modules and chassis

Status Operating Codes for
Normal Operating
Conditions

COMM
LED

FAULT
LED

Status
Display

Operating Condition

on

off

Normal RIO Communications

off

off

No RIO Communications

(1)

off

off

Partial RIO Communications

(2)

off

off

Processor Lockout is Preventing RIO
Communications

(1)(3)

flashing

off

Reset, Adapter Decide Commands

(1)

flashing

off

Reset, Adapter Reset Commands

(1) When the 1747-ASB module is holding outputs in their last state, the Status Display alternates between

the operating indication and HLS.

(2) Some, but not all of the 1747-ASB module's logical devices are receiving RIO link communications from the

scanner. The 1747-ASB module is returning valid input data to the scanner, but is not turning outputs on or
off.

(3) The 1747-ASB module is locking the processor out while it is trying to communicate with all of the

1747-ASB module's logical devices.