Link wiring, Link wiring -2 – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 80

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

5-2 Installation and Wiring

2. Slide the module into the chassis until the top and bottom tabs

lock into place. To remove the module, press and hold the
release located on each self-locking tab and slide the module
out.

3. Cover all unused slots with the Card Slot Filler, Catalog Number

1746-N2.

The modules are connected in a daisy chain configuration on any RIO
link. A daisy chain network is formed by connecting network devices
together in a serial manner using Belden 9463 cable. Belden 9463
cable is the only approved cable for Allen-Bradley RIO links.

Link Wiring

The total number of adapters allowed on the RIO link are:

32 if the scanner and all adapters on the RIO link have extended
node capability

16 if the scanner or any adapter does not have extended node
capability

Refer to page 1-8 for information on extended node capability.

There are no restrictions governing the spacing between the devices,
as long as the maximum cable distance is not exceeded. Refer to the
table below for baud rate and maximum cable distances.