Publication 1747-UM006B-EN-P - June 2003

2-2 Quick Start for Experienced Users

Procedures

1.

Check the contents of shipping box.

Reference

Unpack the shipping box making sure that the contents include:

Remote I/O adapter module (Catalog Number 1747-ASB)

user manual (Publication 1747-6.13)

If the contents are incomplete, call your local Rockwell Automation representative for
assistance.

-

2.

Ensure your chassis supports placement of the 1747-ASB module.

Reference

Check to see that your chassis supports placement of the adapter module by:

reviewing the power requirements of your system (The adapter consumes 600 mA
at 5VDC.)

calculating the total load on the system power supply using the procedure described
in Appendix B

Appendix A

(Specifications)

Appendix B

(Understanding

your

SLC 500/1746

Control System)

3.

Choose the type of slot addressing you will use.

Reference

Select 1747-ASB addressing (i.e., 2-slot, 1-slot, or 1/2-slot). A configuration worksheet is
included in appendix D to assist you in 1747-ASB image table addressing.

Important: Due to SLC and PLC addressing differences, when the 1747-ASB module is used
with an SLC processor, the image bit numbers are 0 to 7, 8 to 15 decimal. When the
1747-ASB module is used with a PLC processor, the image bit numbers are 0 to 7, 10 to 17
octal.

Chapter 3

(Addressing)

Appendix D

(DIP Switch and

Address

Configuration

Worksheets)

4.

Configure the module using the DIP switches.

Reference

Set the DIP switches (located on the printed circuit board) to the desired setting. A
worksheet is included in appendix D to assist you in DIP switch configuration.

Chapter 4
(Configuration)

Appendix D
(DIP Switch and
Address
Configuration
Worksheets)