Appendix b, Appendix, Image size selection (page 4-10) – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 141

Advertising
background image

1

Publication 1747-UM006B-EN-P - June 2003

Appendix

B

Differences Between the 1747-ASB Module
and the 1771-ASB Series C Module

This appendix examines the differences between Catalog Number
1747-ASB and Catalog Number 1771-ASB Series C, Revision E or later.
These differences are:

image size selection

hold last state operation

specialty I/O module mapping and control

remote expansion chassis

starting logical group number selection

inserting and removing I/O modules under power

DIP switch locations

I/O module keying

physical slot numbering

status indication

throughput performance

inhibit functionality

Page and chapter references are provided within each heading so you
can quickly review the information specific to Catalog Number
1747-ASB.

The 1771-ASB image size is automatically selected based on the
chassis size and addressing mode. The automatic assignment is
possible because the number of 1771 chassis physical slots are
provided in 2-group multiples. Therefore, there are no unused
physical I/O slots or scanner image that is not utilized.

Image Size Selection
(page 4-10)

The 1747-ASB image size must be selected with DIP switches
(SW2-5,6,7,8). The selection is necessary because the 1746 chassis are
not provided in 2-group multiples. In some cases, you must make a
choice between not using a slot or not using scanner image. For more
information on odd size chassis and image conditions, refer to page
4-13.

Advertising