Application example program -15, Application example program – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 119

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

Application Examples 8-15

Application Example Program

Shown below is an excerpt from the user program. When the switch is
closed, bulbs 1 and 2 turn on and the decimal value 5555 is moved to
analog output 1 and is converted to an analog signal.

The following is another representation of what is discussed above.

This application consists of a PLC-5/40 processor controlling local and
remote I/O.

] [

I:3.17

1

( )

O:3.0

MOV

MOVE
Source

5555

Dest

O:3.15

12

( )

O:3.19

12

Switch

(1)

Meter

Bulb 1

(2)

Bulb 2

(1) Input bits 16–31 must be converted to 0–15 by subtracting 16. Therefore, Input bit 17 is converted to 1.

(2) Input and Output bits 0–7 must be converted to 8–15 by adding 8. Therefore, Input bit 12 is converted to 4.

0

1

2

3

0

1

2

3

4

5

6

0

1

2

3

SLC 5/02

1746-OW8

1746-IA8

1747-SN

ASB 1

1746-NIO4I

1746-IV32

1746-OV32

1746-OB16

1746-OA16

ASB 2

1746-OA8

1746-IO12

1746-IA16

EMPTY

RediPANEL

The meter is connected
to output 1.

The switch is connected
to input 17.

Bulb 2 is connected
to output 12.

Bulb 1 is connected
to output 4.