Troubleshooting chapter 7 – Rockwell Automation 1771-PM , D17716.5.18 U MNL 1771-PM CLUTCH/BRAKE MOD User Manual

Page 106

Advertising
background image

Troubleshooting

Chapter 7

7Ć22

CAM LIMIT SWITCH Ć TRANSITION TO NEAR TOP ZONE MESSAGES (cont'd)

HEX

CODE

TYPE

PROBLEM

CORRECTIVE ACTION

0A6

0A7

L

RUNĆON CAM SWITCH BOUNCED OR MOTION REVERSED"

(ALT CHASSIS)

During single stroke or continuous mode, only forward motion is

allowed. The PM saw that it was in transition to the near top

zone, and then saw the runĆon cam input come back on possible

showing reverse motion.

See Standard Corrective Action **. Also check for proper

clutch operation.

DIAGNOSTIC MESSAGES

F1

L

LOST COMMUNICATION BETWEEN 1771ĆPM MODULES"

Check rack communication cable. Cycle rack power.

F2

L

LOST COMMUNICATION TO PROGRAMMABLE

CONTROLLER"

Check rack communication cable. Check for proper rack

and scanner configuration. Check for potential electrical

noise problem. Cycle rack power.

AA

L

ALL CAM SWITCHES TURN OFF.

1. Disconnected ground to 1771ĆIA module. Disconnected

power to CAM switches,. disconnected swingarm to

1771ĆIA. bad 1771ĆIA module.

2.

Press ResetĆlatchedĆmsg PB.

A8

N

CAM SWITCHES CANNOT DETECT SHAFT POSITION.

Same as AA except not a latchedĆmessage code.

A9

N

ALL CAM SWITCHES ARE OFF. NEVER DETECTED ON.

Same as A8.