PC Ladder Programming

Chapter 4

4Ć8

Your ladder diagram program can send four commands to the clutch/brake
controller by setting command bits 10-13 in the output image word for
module group (MG) 7, Slot 1 for I/O chassis A and B:

Command

Bit

Press enable

StopĆonĆtop

Reset latched messages

Lamp test

10

11

12

13

These commands can be issued manually by an operator pushing a switch,
or automatically by a switch closure in your machinery. They function as
follows:

Output

Status

Condition Controlled by PM Module

Press Enable

Bit 10

must be ON

OFF

To enable motion in any mode

Immediately turns OFF triac outputs

StopĆonĆtop

(Continuous mode, only)

Bit 11

offĆtoĆon

transition

must be OFF

Turns OFF solenoid outputs the next time the

runĆon cam switches open

To start or maintain continuous stroking

Reset Latched Message

Bit 12

offĆtoĆon

transition

1

Clears any latched or tripped message code

shown in MG 5, Slot 1, as long as the condition

that caused the message no longer exists.

Lamp Test

Bit 13

ON

OFF

Turns ON all these outputs

Brake Fault , Run Window, MicroĆinch Message,

and other diagnostic message lamps

Turns OFF these outputs

1

Holding this bit ON may inhibit the capture of subsequent L or t messages.

Bit addresses for these command bits are shown in Figure 4.2. Example
PLC command rungs are shown in Figure 4.6 through Figure 4.8.

To enable these commands, write ladder program rungs that are
conditioned with examine-on/examine-off instructions to monitor
corresponding switch inputs wired to I/O chassis C. You can use any
available discrete module terminals (excluding those in chassis A or B)
for these inputs (Figure 6.15). For additional information refer to chapter
6, Inputs to Chassis C .