Field Wiring Arm Connections

Chapter 6

6Ć5

Connect optional hardwire inputs as needed to chassis A and B so voting
processors can monitor any of the following inputs:

Input

Terminal

MG

Slot

Figure

Main Valve Stem

Motion Detector

Air Pressure

Auxiliary Valve Stem

MicroĆinch Valve Stem

MicroĆinch Air Pressure

Dump Valve Stem

0

1

2

7

1

2

4

2

2

2

2

5

5

4

0

0

0

0

0

0

1

6.2 or 6.6

6.4 or 6.8

6.4, 6.8

6.4, 6.8

When connected these inputs function as follows:

Triac Command

ON

OFF

Triac Feedback

ON

OFF

ON

OFF

OFF

ON

For additional valve stem requirements, see section title Internal/External Fault Detection

0Ć100ms

0Ć100ms

Air Pressure Feedback

Valve Stem Feedback

Applies to firmware revision A/D and later

Applies to Main, MicroĆInch, Auxiliary, and Dump (if configured) solenoids

Applies to Main, Auxiliary, Dump, and MicroĆinch valves

OFF

0 Ć 100ms

[1]

[2]

[5]

[6]

0Ć510ms

[3]

[4]

0Ć200ms

[4]

0Ć500ms

[4]

0Ć4 seconds

[4]

[7] [8]

Motion Detector must turn ON before upstroke

(before TopĆstopĆcheck cams turn OFF

[1]

[2]

[3]

[4]

[5]

[6]

[7]

[8]

Time window for faultless operation measured from Triac Command offĆtoĆon transition

Time window for faultless operation measured from Triac Feedback offĆtoĆon transition

Time window for faultless operation measured from Valve Stem feedback offĆtoĆon transition

Time window for faultless operation measured from onĆtoĆoff transition of the Triac Command.

OnĆtoĆoff transitions need not occur sequentially.

Motion Detector transition offĆtoĆon is position dependent, onĆtoĆoff is time dependent

Optional Hardwire Inputs