Voting Processor Firmware

Chapter 5

5Ć8

Figure 5.4

Operational Sequence for Upstroke in Single Mode

Start upstroke.

From figure 5.3

Upstroke continues regardless of

releasing RUN buttons

Have both voting processors

detected that antiĆrepeat cams

have opened?

Has onĆtheĆhop been enabled?

Has the shaft moved into its

nearĆtop position?

Have all operators released all RUN

buttons?

NOTE: The shaft continues automatically through its upstroke, then stops. If onĆtheĆhop has

been enabled, operators can start another downstroke without stopping at the top. Do this by

releasing all RUN buttons after the downstroke. Then, press all RUN buttons after the antiĆrepeat

contacts open on the upstroke.

12263

Yes

No

Yes

Both voting processors

deĆenergize their solenoid triacs

to stop the shaft. A stop condition

mesage is displayed.

Has the shaft moved into its

nearĆtop position?

No

Has each operator pressed his RUN

buttons simultaneously, and within 5

seconds for all stations?

Has the shaft moved into its nearĆtop

position?

Has an operator released a RUN

button?

No

Yes

No

Yes

Yes

Yes

No

Yes

Both voting processors

deĆenergize their solenoid triacs

to stop the shaft in its nearĆtop

position

WARNING: If the shaft coasted

past its nearĆtop position while

braking, the brake is faulty and

hazardous. Repair it immediately.

Start onĆtheĆhop downstroke.

Go to figure 5.3

Has the shaft moved into its nearĆtop

position?

No

No

Yes

Yes

No