Field Wiring Arm Connections

Chapter 6

6Ć2

Use This

Mandatory

Figure

For These Connections

6.9

Cam Limit Switch Assemblies

6.10

Main Motor Forward

Barrier Guard

StopĆonĆtop

Arm Continuous

Mode Select Switch

6.11

Operator Stations 1 & 2

Dummy Plugs

Inch Pushbutton Switches

WARNING: To guard against injury to personnel and
damage to your press, connect your clutch/brake controller
exactly as shown in these figures.

The connections for optional features are shown in the following figures:

Use this Figure

For These Optional Connections

6.2 or 6.6

6.4 or 6.8

6.12

6.13

6.14

Switches on

Main Valve Stems

Air Pressure Sensors

Motion Detector

Dump and/or MicroĆinch Valves

Operator Stations 3 & 4

Dummy plugs

Diagnostic Message Display

Brake Fault Indicator

Run Window Indicator

MicroĆinch Indicator

Important: Use 14 AWG stranded copper wire with 3/64-inch insulation
for all solenoid and relay coil connections to the 1771-OD modules. We
also recommend the same wire size for all field wiring arm connections.