Voting Processor Firmware

Chapter 5

5Ć4

Figure 5.1

Cam Limit Switch Settings

Near Top

Position

Run - On

Near Bottom

Zone

Upstroke

Anti - Repeat

before run-on contacts make, or the controller faults.
Run-on contacts must make (not necessarily at the same time)

before

Anti-repeat contacts must break for at least 70ms during

upstroke, then make before run-on contacts break, or the controller faults.
Anti-repeat contacts must make (not necessarily at the same time)

before run-on contacts break, or the controller faults.
Run-on contracts must break (not necessarily at the same time)

MAKE

MAKE

MAKE

BREAK

MAKE

MAKE

BREAK

MAKE

MAKE

MAKE

MAKE

BREAK

MAKE

MAKE

BREAK

BREAK

BREAK

BREAK

Down-

stroke
Near

Bottom
Up-

stroke

Near

Top

Run-On Anti-

Repeat

Zone

Comments

Cam Linit Switch Settings

Refer to Diagnostic Messages, table 7.C. Hex codes 80 thru AA, for descriptions of faults caused

by cam limit switches.

12970

70 ms

NOTE:

Install two mechanically independent cam limit switch assemblies each with three cams and three

limit switches. Set the assemblies to similar settings according to the requirements of your press.
You can set cam limit switches to other configurations provided they meet the make/break conditions

listed below:

Downstroke

Top-Stop

-Check

TopĆstopĆcheck contacts must make (not necessarily at the same time)

TopĆstopĆcheck contacts break, or the controller faults.

TopĆstopĆcheck contacts must break (not necessarily at the same time)

before antiĆrepeat contacts break or the controller faults.

before TopĆstopĆcheck contacts make or the controller faults.

Top-stop-

check

Table 5.A

Operation of Cam Limit Switches

This

Cam

In this

Mode

With these

Conditions

Provides the PM Module a Signal:

AntiĆ

Repeat

OnĆtheĆhop single

stroke

Run buttons released

past bottom

To allow a second stroke when run buttons

are pressed a second time

RunĆon

Inch and MicroĆinch

(forward) and Single

stroke

Cam opens at nearĆtop

position

To turn OFF triac output for

stopĆonĆtop (cycle stop)

Continuous

Cam opens at nearĆtop

position after

stopĆonĆtop command

Single stroke and

Continuous

Cam closes at

nearĆbottom position

To let operator release any depressed run

buttons without interrupting a single stroke

or continuous stroking

TopĆStop

Check

any

Cam closes during

stopĆonĆtop

To energize a Brake Fault output to warn

that the brake is faulty (Hazardous

Condition)

Inch and

MicroĆinch

(reverse)

Cam opens in nearĆtop

position

To turn OFF solenoid outputs to stop the

cycle