SmartPanel Configuration and Installation Guide

Page 11

© 2002-8 SP Controls, Inc. 930 Linden Avenue South San Francisco CA 94080

w

ww.spcontrols.com

Manually placing the Panel in download-only mode

The Panel is manually placed in download-only mode by pressing and holding the On, Off and
Selection Four buttons while applying power. This combination of keys was chosen because it is
unlikely to occur by accident.

Manual activation of download-only mode facilitates reconfiguration should serious corruption of
configuration memory occur.

Restoring normal operation after using download-only mode

Download-only mode is exited by removing and restoring power to the Panel.

If download-only mode was entered automatically because a problem was detected by Panel
firmware self checks, that problem must be remedied before the Panel will function normally. In
most cases, re-downloading the appropriate Driver and configuration restores normal operation.

If the Panel is unable to complete a download session in download-only mode, or persists in
automatically entering the mode whenever powered on, it may have developed hardware
problems and require service.