Page 58

SmartPanel Configuration and Installation Guide

www.spcontrols.com

© 2002-8 SP Controls, Inc. 930 Linden Ave. So. San Francisco CA 94080

Wiring the Relays

Note: All SmartPanel relays are low

voltage only rated at 500mA max
current. Under no circumstances is
high voltage to be connected to
the panel or come into any conduit
or backbox that the Panel uses.

The exact wiring of the relays depends
on your needs and the switching
configuration. Relay configuration using
the Configuration Utility is discussed in
Relays.

Note: Commons may have to be

combined when many relays
communicate with the same
device. Remember that commons
are not true ground (as relay
closures are electrically isolated
from ground and from one
another).

Note: Never combine the commons of two separate controlled devices. This may cause an

electrical short within one or both devices!

RELAYS

PWR

ON

MAINT.

PWR

ON

MOM.

PWR

OFF

MOM.

1A

1B

3A

3B

2A

2B

4A

4B

6A

6B

5A

5B

7A

7B

SELECTION

(EXT. SWITCHER CTRL)

4

3

2

1

500mA MAX. CURRENT

Common

Closures

To devices

controlled by

power relays

To switcher

controlled by

selection relays

Figure 28: Wiring relays