V/f

V/f w/PG Open Loop

Vector

Flux

Vector

10

VS-616G5 Programming Manual

Use this parameter to reset the inverter to its factory default settings. Initialize the inverter after chang-
ing the control PCB, or after selecting language (A1-00), control method (A1-02), or inverter capacity

(O2-04).

Parameter A1-04 is used to enter a password into the inverter, to be able to make adjustments to locked param-

eters.


Password protection is provided for:
A1-01 Access Level
A1-02 Control Method
A1-03 Initialization
A2-01 to A2-32 User Parameters (If selected)

A1-03 Operator Status

Init Parameters

Q

Q

Q

Q

Setting

Description

0

No Initialization (factory default)

1110

User Initialization - resets the inverter to user-specified initial
values. To set user-specified initial values, make all required
changes to parameter settings, then set O2-03 to “1”. The
inverter will memorize all current settings as the user-specified
initial values. Up to 50 changed parameters can be stored.

2220

2-Wire Initialization - terminal 1 becomes FWD run command
and terminal 2 becomes REV run command. All other param-
eters are reset to their original factory default settings.

3330

3-Wire Initialization - terminal 1 becomes run command, termi-
nal 2 becomes stop command and terminal 3 becomes FWD/
REV run selection. All other parameters are reset to their orig-
inal factory default settings.

A1-04 Password Entry

Enter Password

Q

Q

Q

Q

Section A: Initialization Parameters

A1 Initialization Set-up