Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 82

Advertising
background image

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

82

VS-616G5 Programming Manual

Section H: Control Circuit Terminals

H1 Digital Inputs

· Forward and Reverse JOG commands (settings: Fwd Jog = “12”, Rev Jog = “13”)

Forward and reverse run jog frequency commands are enabled.

Notes:

1. When either the forward or reverse jog command is input during run, this command has

priority.

2. When both the forward and reverse jog commands are closed for more than 500ms, the

inverter stops according to the stopping method selection (Bl-03).

3. The forward and reverse jog commands can be set independently.

· Fault Reset (setting: “14”)

Closing this contact resets a fault after the condition is removed.

· Fast-Stop (Set value = 15)

Open: The inverter operates normally.

Closed: The inverter decelerates to stop using deceleration time C1-09 (factory set to 10 sec.). The

run command can remain closed during this period of time. The inverter will not run, from the
external terminals or the digital operator as long as this input is closed.

To restart the inverter, the run command must be cycled.

· Motor 2 Select (Set value = 16)

Open: Motor 1 is selected.

Closed: Motor 2 is selected.

When Motor 2 is selected, the following parameters are effective;

The inverter must be stopped to switch motors.

A multi-function digital output may be programmed when motor 2 is selected. Refer to page 88
for more information.

· Fast-Stop (setting: “17”)

<1110>

When this input is closed the motor decelerates to a stop using the rate defined by parameter C1-09.

· Timer Function (Set value = 18)
The timer function works independently from the inverter.
The timer input must be on longer than the time in b4-01for the output to close.
The timer input must be off longer than the time in b4-02 for the output to open.

b4-01 is the on-delay time setting (0.0 - 300.0 second)
b4-02 is the off-delay time setting (0.0 - 300.0 second)

Setting

Description

12

Forward jog command is closed, run at jog frequency ref-
erence (D1-09).

13

Reverse jog command is closed, run at jog frequency ref-
erence (D1-09).