VS-616G5 Programming Manual

85

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

· PID Integral reset (Set value = 30)

Open: PID Integral values are added.
Closed: PID Integral value is set to zero.

· PID Control Integral Hold (Set value = 31)

<1110>

Closed: Integral value of the PID control is held.

· DC Injection Braking Command (setting: “60”)

When a DC injection braking command is input while the inverter is stopped, DC injection braking
operation is activated. When a run command or a jog command is input, DC injection braking is
released to start operation (operation has priority).

H1-__ = “24”

Depress the Data/Enter key.

Input Level Selection

Detection Method

External Fault Action

N.O. Contact
N.C. Contact

Always

During Run

Ramp to Stop
Coast to Stop
Fast-stop

Depress

Alarm Only

the

key.

DC Injection Braking Command

Fwd Run Command

ON

OFF

OFF

Output Frequency

ON

OFF

OFF

DC Injection

Braking

DC Injection

Braking

DC Injection Braking

Start Frequency

(B2-01)

Figure 35 DC Injection Braking Contact Input Timing Diagram

Section H: Control Circuit Terminals

H1 Digital Inputs