Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 88

Advertising
background image

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

88

VS-616G5 Programming Manual

Section H: Control Circuit Terminals

H2 Digital Outputs

· KEB Ridethrough (settings: N.C. = “65”, N.O. = “66”)

In general applications, the Kinetic Energy Braking (KEB) control circuit attempts to maintain the
DC bus voltage at an optimum level [1.35 × input voltage (E1-01)] during momentary power loss, by
using load inertia to regenerate voltage back to the DC bus. The inverter decelerates at the fast-stop
rate (C1-09), until power is restored, or until the time runs out and an undervoltage fault (UV)
occurs. The larger the inertia, the longer the deceleration rate can be extended. If the inertia is small,
then the inverter must decelerate quickly to regenerate voltage back to the DC bus, and thus the ride-
through time is shorter. For most applications, set KEB Frequency Constant (L2-06) to “0” (factory

default).
.

Note:

Larger model inverters (2022 and above, 4018 and above) require a separate uninterruptible
power supply (UPS) for control power, in order for load inertia ridethrough to be effective.

H2

Digital Outputs
The VS-616G5 has three multi-function contact outputs for the indication of various conditions,
including frequency detection, speed agree, zero speed, overtorque detection, and many others. This
section includes descriptions of these functions.

The following table lists the function selections for the multi-function contact outputs (terminals 9, 25
and 26), and indicates the control modes during which each function can be enabled.

H2-01 Multi-function Output 1 Selection (terminal 9, 10) Terminal 9 Sel

B

B

B

B

H2-02 Multi-function Output 2 Selection (terminal 25, 27) Terminal 25 Sel

B

B

B

B

H2-03 Multi-function Output 3 Selection (terminal 26, 27) Terminal 26 Sel

B

B

B

B

H2-01

to 3

Setting

Function

Control Method (A1-02)

Reference

Page

V/f

V/f w/ PG

Open Loop

Vector

Flux Vector

0

During run 1 (factory default, H2-01)

1

Zero-speed (factory default, H2-02)

2

Frequency agree 1 (factory default, H2-03)

3

Desired frequency agree 1

4

Frequency detection 1

KEB Ridethrough

ON

OFF

Output Frequency

L2-06

C1-09

OFF

C1-01

Figure 36 KEB Ridethrough Timing Diagram

Multi-function Input Contact

(H1-__ = “65” or “66”)

1.35 × E1-01

Advertising