VS-616G5 Programming Manual

35

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

Parameter C3-05 determines if the motor torque characteristic is based on output frequency or motor
speed.

When running the motor only in the constant torque region, leave parameter C3-05 set to 0 for the
best performance.

When running the motor in the constant horsepower region, set parameter C3-05 to 1 because the
larger flux will result in better motor stability.

C3-04 Slip Compensation During Regeneration

Slip Comp Regen

A

-

A

-

Setting

Description

0

Slip compensation disabled during regeneration (factory default)

1

Slip compensation enabled during regeneration

C3-05 Flux Calculation Method

Flux Select

-

-

A

-

Setting

Description

0

Slip Included
Motor torque characteristic is based on frequency. (factory default)

1

Slip Excluded
Motor torque characteristic is based on motor speed.

60Hz 1800 rpm 120Hz 3600 rpm

=1

=0

=0

=1

Torque

100%

0 %

Section C: Tuning Parameters

C3 Motor Slip Compensation