V/f

V/f w/PG Open Loop

Vector

Flux

Vector

78

VS-616G5 Programming Manual

Section H: Control Circuit Terminals

H1 Digital Inputs

· Local/Remote Selection (setting: “1”)
Selects the operation mode, only when the inverter is stopped.

Local:

Operation according to frequency reference and run command from digital operator.

Remote: Operation according to frequency reference and run command set by B1-01 and B1-

02, respectively.

Note:

When local/remote selection is set by a multi-function contact input terminal, local/remote
selection from the digital operator key is disabled.

· Option/Inverter Selection (setting: “2”)

Selects whether operation is performed using a reference command from an option card or from the
inverter. Selection is effective only when the inverter is stopped.

Open:

Runs by frequency reference and run command from inverter control circuit termi-
nal or digital operator.

Closed:

Runs by frequency reference and run command from an option card.

Multi-Step Ref 1 through 3 and Jog Freq Ref (Set value = 3, 4, 5, and 6)

O - Open
X - Closed
-- Has no effect
d1-01 is effective when b1-01 is set to 0 (reference from the digital operator)
d1-02 is effective when the terminal 16 setting (H3-05) is set to anything other than zero.

Terminal 8

Terminal 7

Terminal 6

Terminal 5

(H1-06 = 6)

(H1-05 = 5)

(H1-04 = 4)

(H1-03 = 3)

Preset

Jog Freq Ref

Multi-Step Ref 3

Multi-Step Ref 2

Multi-Step Ref 1

Reference

O

O

O

O

Reference 1 (d1-01)

O

O

O

X

Reference 2 (d1-02)

O

O

X

O

Reference 3 (d1-03)

O

O

X

X

Reference 4 (d1-04)

O

X

O

O

Reference 5 (d1-05)

O

X

O

X

Reference 6 (d1-06)

O

X

X

O

Reference 7 (d1-07)

O

X

X

X

Reference 8 (d1-08)

X

Jog Reference (d1-09)