Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 45

Advertising
background image

VS-616G5 Programming Manual

45

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

D

Reference Parameters

D1

Preset References

Setting Range:

0.0 to 400.0Hz

Factory Default:

0.0Hz

Up to 9 preset speed references (including jog) can be set through multi-function contact input func-
tion selections. When using the multi-step speed references, set the reference selection (B1-01) to “0”,
and set terminal 16 selection (H3-05) to “1F”. See the following table for programming preset speed
references.

D1-01 Preset Frequency Reference 1

Reference 1

Q

Q

Q

Q

D1-02 Preset Frequency Reference 2

Reference 2

Q

Q

Q

Q

D1-03 Preset Frequency Reference 3

Reference 3

Q

Q

Q

Q

D1-04 Preset Frequency Reference 4

Reference 4

Q

Q

Q

Q

D1-05 Preset Frequency Reference 5

Reference 5

B

B

B

B

D1-06 Preset Frequency Reference 6

Reference 6

B

B

B

B

D1-07 Preset Frequency Reference 7

Reference 7

B

B

B

B

D1-08 Preset Frequency Reference 8

Reference 8

B

B

B

B

Terminal 5

H1-03

= “3”

Terminal 6

H1-04

= “4”

Terminal 7

H1-05

= “5”

Terminal 8

H1-06

= “6”

Speed Reference

Open

Open

Open

Open

Speed Reference 1 - Set Reference Source
(B1-01)

to “0”.

Closed

Open

Open

Open

Speed Reference 2 - Set Terminal 16 Selection
(H3-05)

to “1F”.

Open

Closed

Open

Open

Speed Reference 3

Closed

Closed

Open

Open

Speed Reference 4

Open

Open

Closed

Open

Speed Reference 5

Closed

Open

Closed

Open

Speed Reference 6

Open

Closed

Closed

Open

Speed Reference 7

Closed

Closed

Closed

Open

Speed Reference 8

Closed

Closed

Closed

Closed

Jog Speed Reference

Section D: Reference Parameters

D1 Preset References