Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 64

Advertising
background image

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

64

VS-616G5 Programming Manual

Section F: Option Parameters

F1 PG Option Set-up

Selects the stopping method when an overspeed condition is detected.

Selects the stopping method when excessive speed deviation is detected.

Sets the relationship between the motor rotation direction and PG polarity.

The motor rotation direction applies when viewing the motor shaft from the load side.

Setting Range:

1 to 132

Factory Default:

1

Sets the division ratio for monitoring the PG pulse signals.

F1-03 Overspeed Detection Stopping Method

PG Overspeed Sel

B

B

Setting

Description

0

Ramp to stop - according to C1-02

1

Coast to stop (factory default)

2

Fast-stop according to C1-09

3

Alarm flashes, operation continues (this setting is disabled
during flux vector control)

F1-04 PG Deviation Detection Stopping Method

PG Deviation Sel

B

B

Setting

Description

0

Ramp to stop - according to C1-02

1

Coast to stop

2

Fast-stop according to C1-09

3

Alarm flashes, operation continues (factory default)

F1-05 PG Rotation Selection

PG Rotation Sel

B

B

Setting

Description

0

Motor FWD direction is counterclockwise (factory default).

1

Motor FWD direction is clockwise.

F1-06 PG Division Rate (pulse output)

PG Output Ratio

B

B