Section F: Option Parameters

F9 CP-916 Option Set-up

F9

CP-916 Setup

The CP-916 option card provides PLC and motion type functions. This allows the G5 inverter to be a
stand alone control system.
The CP-916 option card connects to the control board at 3CN.
When the CP-916 option is installed, the 4CN speed feedback option port is the only option port that is
supported.

Specifications
• RS 232C communication port - Used for programming the CP-916G and for communication to
other devices such as PLC’s or printers.
• High speed (4 Mb/s) peer to peer communication port.
• Available protocol;
MEMOBUS (MODBUS) 19.2 kbps maximum.
Application Download Tool 19.2 kbps maximum.
CP 717 Programming Tool 9.6 kbps.

Parameter F9-01 selects the initial state for an external fault condition when the inverter is configured
for serial communication using the CP-916.

The “EFO” fault code will be displayed.

Parameter F9-02 selects the condition of detection for an external fault when using the CP-916 option.

F9-01

Option External Fault Selection

EFO Selection

A

A

A

A

Setting

Description

0

When closed, the inverter will trip. (factory default)

1

When open, the inverter will trip.

F9-02

Option External Fault Detection

EFO Detection

A

A

A

A

Setting

Description

0

The fault will always be detected, even when the drive is
stopped. (factory default)

1

The fault will be detected only when the drive is running.