VS-616G5 Programming Manual

49

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

D5

Torque Control

Selects between speed and torque control during flux vector operation (A1-03 = “3”).

Speed/torque control selection can also be made by using a multi-function contact input function selec-
tion (H1-__ = “71”).

Setting Range:

0 to 1000ms

Factory Default:

0ms

Sets delay time constant for torque reference input in the torque control mode, in units of 1ms.

Sets speed limit selection in the torque control mode.

Setting Range:

-120 to 120%

Factory Default:

0%

Sets the speed limit value in the torque control mode as a percentage of the maximum output fre-
quency, when D5-03 = “2”.

D5-01 Torque Control Selection

Torq Control Sel

-

-

-

A

Setting

Description

0

Speed control enabled with torque limit (factory default)

1

Torque control enabled with speed limit

D5-02 Torque Limit Primary Delay Time

Torq Ref Filter

-

-

-

A

D5-03 Speed Limit Input Selection

Speed Limit Sel

-

-

-

A

Setting

Description

1

Speed limit is the analog speed reference set by
terminal 13 or 14 (factory default).

2

Speed limit is the reference set by B1-01.

D5-04 Speed Limit Value

Speed Lmt Value

-

-

-

A

Section D: Reference Parameters

D5 Torque Control