Section L: Protection Parameters

L3 Stall Prevention / Current Limit

Setting Range:

0 to 200%

Factory Default:

150%

The stall prevention/current limit level during acceleration is set as a percentage of inverter rated cur-
rent. A setting of 200% disables current limit during acceleration. During acceleration, if the output
current exceeds this current limit level (L3-02), acceleration stops and frequency is maintained. When
the output current decreases below this current limit level (L3-02), acceleration restarts.

When a motor is used in the constant output area (constant HP), output frequency

max. voltage out-

put frequency (E1-06). In this area, the stall prevention/current limit level during acceleration is auto-
matically reduced for smoother acceleration. This parameter limits the stall prevention/current limit
level during acceleration in the constant output area so that it does not decrease unnecessarily. The
current limit level during acceleration is changed according to the following equation:

L3-02

Stall Prevention Level During Acceleration

StallP Accel Lvl

B

B

B

L3-03

Stall Prevention Limit (constant output area)

StallP CHP Level

A

A

A

Motor Current

L3-02

Time

Output Frequency

Time

*

* Controls the acceleration rate to

prevent the inverter from tripping.

Figure 52 Stall Prevention/Current Limit During Acceleration

Current Limit Level During
Accel in Constant Output Area

Current Limit Level During
Acceleration (L3-02)

Max. Voltage Output Frequency (E1-06)

Output Frequency

×

=