VS-616G5 Programming Manual

83

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

a - b4-01 b - b4-02

· PID Disable (Set value = 19)

Open: PID control is enabled.

Closed: PID control is disabled

· Program Lockout (setting: “1B”)

Opening this contact prohibits the changing of VS-616G5 parameters.

· TrimCtl Increase (Set value = 1C)
· TrimCtl Decrease (Set value 1D)

Closed: Increases or decreases the output frequency based on the setting of d4-02 (trim control

level). This function is not available when the reference is set from the digital operator.

· Analog Reference Sample/Hold Selection (setting: “1E”)
If the contact input closes for 100ms or longer, the analog frequency reference is sampled once, after
which the analog frequency reference is held.

Note:

t1, t3 - Reference is held at 100ms or longer.
t2 - Reference is not held at less than 100ms.

a

b

b

a

Multi-function Digital
Input: Timer Function

Multi-function Contact
Output: Timer Function

Figure 34 Sample/Hold Selection - Analog Reference

Analog Input

Fref

100ms

100ms

t1

t2

t3

Open

Closed

Section H: Control Circuit Terminals