Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 67

Advertising
background image

VS-616G5 Programming Manual

67

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

Setting Range:

0.0 to 10 seconds

Factory Default:

2 seconds

Parameter F1-14 sets the time from when the pulse generator (PG) signal is missing to when the fault
signal is displayed.
The stopping method when a “PGO” fault is detected is selected by parameter F1-02.
If a speed reference is commanded, but the motor is physically locked, a “PGO” fault will occur even
though the PG is not disconnected from the inverter.

F2

AI-14B Set-up

Sets CH1 to CH3 input functions when AI-14B option is connected.

When the 3CH individual input is used, parameter B1-01 is automatically set to “l” (frequency refer-
ence from control circuit terminal). The option/inverter reference selection, which is selected by a
multi-function contact input (H1-__ = “2”), is disabled when using the AI-14B option.

F1-14 PGO Detection Time

PGO Detect Time

A

A

F2-01 Bipolar or Unipolar Input Selection

AI-14 Input Sel

A

A

A

A

Setting

Function

CH1 (TC1 to TC4) CH2 (TC2 to TC4) CH3 (TC3 to TC4)

0

3-channel individual

input (factory default)

Substitute for

terminals 13 and 17

Substitute for

terminals 14 and 17

Substitute for

terminals 16 and 17

1

3-channel additional

input

Sum of CH1 to CH3 input values is used as the frequency
reference value.

Section F: Option Parameters

F2 AI-14B Option Set-up