90

VS-616G5 Programming Manual

Section H: Control Circuit Terminals

H2 Digital Outputs

· Frequency Agree 1 (setting: “2”)

Closes whenever the output frequency “agrees” with the frequency reference, plus or minus the
speed agree detection width (L4-02). This is effective during both forward and reverse operation.

· Desired Frequency Agree 1 (setting: “3”)

Closes whenever the output frequency “agrees” with the speed agree detection level (L4-01), plus or
minus the speed agree detection width (L4-02). This is effective during both forward and reverse
operation.

· Frequency Detection 1 (setting: “4”)

Closes whenever the output frequency is at or below the speed agree detection level (L4-01). During
acceleration from below the detection level, the output frequency increases through the detection
bandwidth (L4-02) before the contact opens again. This is effective during both forward and reverse
operation.

Detection Width 1 (L4-02)

Output Frequency

Frequency Agree 1 Signal

ON

Frequency Reference

Figure 37 Frequency Agree Signal 1 Timing Diagram

OFF

OFF

Detection Width 1 (L4-02)

Output Frequency

Desired Frequency

ON

Detection Level 1 (L4-01)

Figure 38 Desired Frequency Agree 1 Signal Timing Diagram

Agree 1 Signal

OFF

OFF

Advertising