VS-616G5 Programming Manual

51

· When [-1 × speed limit bias (D5-05)] < motor speed < [speed limit + D5-05], torque control is acti-

vated using the set torque reference.

· When motor speed > [speed limit + D5-05], torque control is activated using the set torque refer-

ence.

· When motor speed < [-l × D5-05], the speed limiting circuit outputs a positive torque reference to

prevent the motor speed from increasing in the reverse direction.

Therefore, when torque reference > 0 and speed limit > 0, the torque control range is:

[-l × D5-05] < motor speed < [speed limit + D5-05]

Refer to the following table for more details on the relationship between torque reference, speed limit
and motor speed.

Winder Control

Unwinder Control

Configuration

Direction of Motor
Rotation

Forward

Reverse

Forward

Reverse

Reference
Polarity

Torque
Reference
(TREF)

+

-

-

+

Speed
Limit
(NLIM)

+

-

+

-

Torque Profile

M

Motor

Line Direction

T

N

M

Motor

Line Direction

T

N

0

D5-05

Speed

NLIM

TREF

Torque

Torque

Limit

Torque

Limit

D5-05

Speed

NLIM

TREF

Torque

Torque

Limit

0

D5-05

Speed

NLIM

Torque

Torque

Limit

0

Torque

Limit

0

D5-05

Speed

NLIM

TREF

Torque

Torque

Limit

Torque

Limit

Section D: Reference Parameters

D5 Torque Control