Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 158

Advertising
background image

158

VS-616G5 Programming Manual

M

on

ito

r

U1-12

Operation Status*
(Int Ctl Sts 1)

Q

Q

Q

Q

U1-13

Elapsed Time*
(Elapsed Time)

1 hour

Q

Q

Q

Q

U1-14

Software No. at FLASH
Side*
(FLASH ID)

Q

Q

Q

Q

U1-15

Control Circuit
Terminal 13
(Term 13 Level)

0.1%

10V/10V

B

B

B

B

U1-16

Control Circuit Terminal
14 Input Voltage (Term 14
Level)

0.1%

10V/10V or

20 mA

B

B

B

B

U1-17

Control Circuit Terminal
16 Input
(Terminal 16 Level)

0.1%

10V/10V

B

B

B

B

U1-18

Motor Secondary
Current (Iq)
(Mot SEC Current)

0.1%

10V/Motor

rated

primary
current

B

B

B

B

U1-19

Motor Excitation
Current (Mot EXC Cur-
rent)

0.1%

10V/Motor

rated

primary

current

x

x

B

B

U1-20

Output Frequency after
Soft-start
(SFS Output)

0.01Hz

10V/Max.

output

frequency

A

A

A

A

U1-21

ASR Input
(ASR Input)

0.01%

10V/Max.

output

frequency

x

A

x

A

U1-22

ASR Output
(ASR Output)

0.01%

Analog monitor output level becomes 10V/Max. out-
put frequency for V/f control mode with PG.

10V/Motor

rated

primary

current

x

A

x

A

U1-23

Speed Deviation
(Speed Deviation)

0.01%

10V/Max.

output

Frequency

x

A

x

A

U1-24

PID Feedback Capacity
(PID Feedback)

0.01%

10V/Max.

output

Frequency

A

A

A

A

Fu

nc

tio

n

Parameter

No.

Name

(Digital Operator Display)

Min.

Unit

Description

Analog

Monitor

Output Level

Parameter Access Level

V/f

V/f w/

PG

Vector

w/o

PG

Vector

w/ PG

1: During running

1: During zero speed

1: During reverse

1: During reset signal input

1: During speed agree

1: Inverter operation ready

1: Minor fault

1: Major fault

0 0 0 0 0 0 0 0

Appendix

VS-616G5 Parameter List U Monitor

* Cannot be changed by U1-04