Analog output channel 1 selection (continued) – Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 69

Advertising
background image

VS-616G5 Programming Manual

69

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

Setting Range:

0.00 to 2.50

Factory Default:

1.00

Sets the channel 1 output gain for the analog output monitors. To obtain the output level, multiply the
monitor output level by the gain value set in F4-02.

18

Motor secondary current (Iq)

Monitors the calculated value of the motors secondary current. (Iq) The motors

rated secondary current corresponds to 100%. 10 V=Rated secondary current.

(0 to + 10 V output)

19

Motor excitation current (Id)

Monitors the calculated value of the motors excitation current. (Id) The motors

rated excitation current corresponds to 100%. 10 V=Rated excitation current. (0

to + 10 V output).

20

SFS output frequency

Monitors the output frequency after a soft start. This is the frequency without the

correction from compensation functions such as slip compensation. 10 V=Max.

frequency (0 to +/- 10 V possible)

21

ASR input

Monitors the input to the speed control loop. The max. frequency corresponds to

100%. 10 V=Max. frequency (0 to +/- 10 V possible)

22

ASR output

Monitors the output from the speed control loop. Analog monitor becomes 10 V/

max. output frequency with V/F control. In vector control the analog monitor be-

comes 10V= motor rated excitation current. (0 to +/-10V possible.)

23

Speed deviation

Monitors the speed deviation within the speed control loop. The max. frequency

corresponds to 100%. 10 V=Max. frequency (0 to +/-10 V possible.)

24

PID feedback

Monitors the feedback value when the PID control is utilized. The input for the

max. frequency corresponds to 100%. 10 V= Max frequency.

(0 to +/-10 V possible.)

25

Not Used

--

26

Voltage reference (Vq output)

Monitors the inverters internal voltage reference value for the motors secondary

current control. 10 V= 200,400 or 575 VAC (0 to =/- 10 V possible.)

27

Voltage reference (Vd output)

Monitors the inverters internal voltage reference value for the motors excitation

current control. 10 V= 200,400 or 575 VAC (0 to =/- 10 V possible.)

28-30

Not Used

--

31

Not Used

--

32

ACR(q) Output

Monitors current control output value for the motors secondary current.

10 V= 100%.

33

ACR(d) Output

Monitors current control output value for the motors excitation current.

10 V= 100%.

34-35

Not Used

--

36

PID Input Monitor

Monitors the input to the PID circuit. This is the PID reference + the PID reference

bias - the PID feedback. 10 V= Max frequency.

37

PID Output Monitor

Monitors the output of the PID circuit. 10 V= Max frequency.

38

PID Setpoint or Reference

Monitors the PID setpoint. This is the PID setpoint + the PID setpoint bias.

10 V= Max frequency.

F4-02 Analog Output Channel 1 Gain

AO CH1 Gain

A

A

A

A

Analog Output Channel 1 Selection (Continued)

F4-01 Setting

Function

Description

Section F: Option Parameters

F4 AO-08/AO-12 Option Set-up

Advertising