Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 121

Advertising
background image

VS-616G5 Programming Manual

121

Selects the monitor to be displayed on the digital operator immediately after the power supply is turned
ON.

Units for parameters and monitors related to frequency can be scaled as shown below.

O1-02 Monitor Selection After Power-up

Power-On Monitor

B

B

B

B

Setting

Description

1

Displays frequency reference (factory default).

2

Displays output frequency.

3

Displays output current.

4

Displays the monitor set in O1-01.

O1-03 Scale for Setting and Monitoring Frequency

Display Scaling

B

B

B

B

Setting

Description

00000

Unit: 0.01Hz (factory default)

00001

Unit: 0.01%

00002 to 00039

Unit: rpm (0 to 3999)

00040 to 03999

(user-selected units)

Digits:

5th

4th

3rd

2nd

1st

0

0

0

0

0

The 1st thru 4th digits determine the set value at 100% output frequency.
Decimal point position is set by the 5th digit as follows:

5th digit = 0: displayed as 0000
5th digit = 1: displayed as 000.0
5th digit = 2: displayed as 00.00
5th digit = 3: displayed as 0.000

Example 1
If 100% output frequency is equal to 200.0 units:
Set O1-03 = “12000”; 100% of this reference is displayed as 200.0 and 60%
of this reference is displayed as 120.0.
Example 2
If 100% output frequency is equal to 65.00:
Set O1-03 = “26500”; 60% of this reference is displayed as 39.00.

Section L: Operator Parameters

O1 Monitor Selection