Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 50

Advertising
background image

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

50

VS-616G5 Programming Manual

Setting Range:

0 to 120%

Factory Default:

10%

Sets the speed limit bias value in the torque control mode as a percentage of the maximum output fre-
quency.

Setting Range:

0 to 1000ms

Factory Default:

0ms

Sets delay time from when the speed/torque control selection is made to when the control mode is
actually changed, in units of 1ms.

Torque Control Operation
To select torque control, set torque selection (D5-01) to “1”, or close the multi-function contact input
set to speed/torque control (H1-__ = “71”) and set terminal 16 function selection to torque reference

(H3-05 = “13”).

*1: When speed limit selection (D5-03) is set to “1”, the master frequency reference input from termi-

nal 13 or 14 becomes the speed limit; when speed limit selection (D5-03) is set to “2”, the set value
of D5-04 becomes the speed limit.

*2: When terminal 14 function selection is set to torque compensation (H3-09 = “14”), terminal l4 set

value can be used as the torque compensation value.

When torque reference > 0 and speed limit > 0 (winder application sequence), the following sequence
is activated:

D5-05 Speed Limit Bias

Speed Lmt Bias

-

-

-

A

D5-06 Reference Delay Timer

Ref Hold Time

-

-

-

A

Speed

1

1 + ST

Torque Limit

Iq

+

+

Figure 27 Torque Control Block Diagram

Limiting

Circuit

SFS

T = D5-02

÷

÷

+

Motor Speed

D5-05

Torque

Compensation

*2

Torque

Reference

Speed Limit

*1

Section D: Reference Parameters

D5 Torque Control

Advertising