Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 102

Advertising
background image

102

VS-616G5 Programming Manual

Section H: Control Circuit Terminals

H5 Serial Communication Set-up

Selects the stopping method after a transmission error is detected.

H5-05 enables or disables the MODBUS time out detection function. After initial communication
begins, if communication is interrupted for longer than 2 seconds, then a communication fault will
occur.
During a communication fault, the following fault code will be displayed: “CE Memobus Com Err”.

L

Protection Parameters

L1

Motor Overload
The VS-616G5 protects against motor overload with a UL-recognized, built-in electronic thermal
overload function.

Selects whether motor overload protection is provided.

The electronic thermal overload function estimates motor temperature, based on inverter output cur-
rent and time, to protect the motor from overheating. When the electronic thermal overload relay is
activated, an “OL1” error occurs, shutting OFF the inverter output and preventing excessive overheat-
ing in the motor. As long as the inverter is powered up, it continues to calculate the motor temperature.

When operating with one inverter connected to one motor, an external thermal relay is not needed.

H5-04 Stopping Method After Communication Error

Serial Fault Sel

A

A

A

A

Setting

Description

0

Ramp to stop according to the time set in C1-02.

1

Fast-stop according to the time set in C1-09.

2

Coast to stop

3

Alarm only, continuous operation (factory default)

H5-05 MODBUS Time Out Detection

Serial Fault Dtct

A

A

A

A

Setting

Description

0

Disabled - Time out detection is disabled.

1

Enabled - Time out detection is enabled.

L1-01

Motor Protection Fault Selection (OL1)

MOL Fault Select

B

B

B

B

Setting

Description

0

Motor overload detection is disabled.

1

Motor overload detection is enabled,
motor coasts to stop (factory default).