2.5.3 Primary Measurement Channel 6 (Temperature)

2.5.3.1

Description of PMC6

In register 2400, a plain text ASCII description of PMC6 is given

Start
register

Number of
registers

Reg1

… Reg8

16 ASCII characters

Modbus
function code

Read
access

Write
access

2400

8

Description of PMC6

3, 4

U/A/S

none

Figure 2.5.3.1.1: Definition of register 2400.

Command: PMC6 text

Modbus address:

2400

Length:

8

Type:

3

Read

Parameter:

Text

Format:

Character

Value:

T

Figure 2.5.3.1.2: Example to read the description. It is

T

”(Temperature).

2.5.3.2

Selecting the Physical Unit for PMC6

In register 2408, the available physical units of PMC6 are defined.

Start
register

Number of
registers

Reg1 / Reg2
(bitwise defined)

Modbus
function code

Read
access

Write
access

2408

2

Available physical units of PMC6

3, 4

U/A/S

none

Figure 2.5.3.2.1: Definition of register 2408.

Command: PMC6 available units

Modbus address:

2408

Length:

2

Type:

3

Read

Parameter:

Units

Format:

Hex

Value:

0x06

Figure 2.5.3.2.2: Example to read the available physical unit for PMC6. K (0x02) + °C (0x04), total

0x06.

In register 2410, the active physical unit of PMC6 can be selected, by choosing one of the physical
units that are defined in register 2408.

Start
register

Number of
registers

Reg1 / Reg2
(bitwise defined)

Modbus
function code

Read
access

Write
access

2410

2

Selected active physical unit of PMC6

16

none

U/A/S

Figure 2.5.3.2.3: Definition of register 2410. Only one bit can be set.

Command: PMC6 set unit

Modbus address:

2410

Length:

2

Type:

16

Write

Parameter:

Unit

Format:

Hex

Value:

0x04

Figure 2.5.3.2.4: Example to set the physical unit of PMC6 to °C (0x04).

Attention:

Changing the physical unit has also an influence on the output of AO1 / AO2, as the same physical unit
is active for the analog outputs. All limits of the 4-20 mA analog output have to be redefined after
changing the physical unit!