pH ARC Sensors Modbus RTU Programmer

s Manual (EPHUM011)

624300/01

page 6 / 67

Command: Operator level

Modbus address:

4288

Length:

4

Type:

3

Read

Parameter:

Operator level

Password

Format:

Hex

decimal

Value:

0x30

0

Figure 2.2.1.4: Example to read the active operator level: the active level is 0x30 (Specialist). The

sensor does not report the password. The value 0 is returned instead.

Command: Operator level

Modbus address:

4288

Length:

4

Type:

16

Write

Parameter:

Operator level

Password

Format:

Hex

decimal

Value:

0x03

0

Figure 2.2.1.5: Example to set the operator level to 0x03 (User). The password 0 has to be sent.

Command: Operator level

Modbus address:

4288

Length:

4

Type:

16

Write

Parameter:

Operator level

Password

Format:

Hex

decimal

Value:

0x0C

18111978

Figure 2.2.1.6: Example to set the active operator level to 0xC (Administrator). The correct password

has to be sent.

Command: Operator level

Modbus address:

4288

Length:

4

Type:

16

Write

Parameter:

Operator level

Password

Format:

Hex

decimal

Value:

0x0B

18111978

Figure 2.2.1.7: Example for a Modbus error. If the level or the password is not correct, (Operator level =

0x0B), the sensor answers with a Modbus error message

Slave device exception response

(see chapter 1.6).

2.2.2 Changing Passwords for Operator Level

The passwords for accessing the operator levels A and S can be modified by S (Specialist) only. U
(User) and A (Administrator) have no right to change any password. The new password will remain
stored after power down.

Start
register

Number of
registers

Reg1 / Reg2

Reg3 / Reg4

Modbus
function code

Read
access

Write
access

4292

4

Level

New password

16

None

S

Figure 2.2.2.1: Definition of register 4292.

Command: Password

Modbus address:

4292

Length:

4

Type:

16

Write

Parameter:

Operator level

Pass number

Format:

Hex

Decimal

Value:

0x30

12345678

Figure 2.2.2.2: Example to set the Password of operator level S (code 0x30) to 12345678.