Burkert Type 8630 User Manual

Page 107

Advertising
background image

8630 - 105

O

PERATING

THE

PROCESS

CONTROLLER

P.Q’LIN

Starting the routine for linearization of the process curve

With the activation of the function

P.CONTRL, the functions P.Q’LIN, which are required for process

control, are copied into the main menu. Via these functions, the program is started for autonomous
determination of the fixed points for a correction characteristic.

The program increases in 20 steps the valve stroke from 0 to 100 % and measures the associated
process variables. The pairs of values of the correction characteristic are stored as a freely
programmable characteristic under the menu item

CHARACT/CHAFREE and may be viewed under this

menu item.

If the menu item

CHARACT was not transferred under the menu item ADDFUNCT to the main menu,

this is done automatically on execution of the function

P.Q’LIN. At the same time, the menu item

CHARACT/CHAFREE is activated.

This function makes sense only when flow control is to be carried out.

➔ You start the routine for linearization of the process characteristic by calling up the menu item P.Q’LIN

in the main menu and pressing the MANUAL/AUTOMATIC key for 5 seconds.

Display

Description

P.Q’LIN 5

Countdown from 5 to 0 for starting

P.Q’LIN 4

der Routine

:

P.Q’LIN 0

¦ P.Q’LIN 0

Display of the fixed point that is being approached at the moment

¦ P.Q’LIN 1

(der Fortgang wird durch einen sich drehenden Balken am linken

¦ P.Q’LIN 2

Rand des Displays angezeigt)

¦ P.Q’LIN 3

:

P.Q’LIN.END

(flashing) End of routine

Q.ERR X.X

Message on occurrence of an error
(shown on the right is the error number - see chapter

Maintenance

process controller)

Display during call-up and execution of the routine

NOTE

The function

P.Q’LIN can only be started when the menu item P.CONTRL / P.COINP /

INP FREQ or item P.CONTRL / P.COINP / INP420 has been selected.