Process value (circular plug m 8) – Burkert Type 8630 User Manual

Page 48

Advertising
background image

46 - 8630

I

NSTALLATION

Input type

No. of

plugs

Pin

Configuration

Jumper

ext. connection

internally

supplied
transmitter*

1

1

2

3 + 4

+ 24 V - supply to transmitter p1
4 ... 20 mA - output from transmitter p1

n.c.

2

1

2

3 + 4

+ 24 V - supply to transmitter p2
4 ... 20 mA - output from transmitter p2

n.c.

Option:
temperature
transmitter

3

1

2

3 + 4

+ 24 V - supply to transmitter
4 ... 20 mA - output from temperature
transmitter

n.c.

* May be set via software (section

Procedure for specifying the basic settings)

**

The jumper is situated on the connection board of the TOP Control Continuous (see next page)

Process value (circular plug M 8)

For line compensation reasons, connect sensor Pt-100 via 3 conductors. PIN 3 and PIN 4
must be bridged at the sensor.

NOTE

Process value with the option flow rate controller (2 circular plugs M8)
Option: with temperature sensor input (3 circular plugs M8)

Input type *

Pin

Allocation

Jumper** External connection

4 ... 20 mA

1

+ 24 V supply transmitter

- internal

2

Output Transmitter

supply

3

GND

4

bridge to GND (GND from
3-conductor transmitter)

4 ... 20 mA

1

not connected

- external

2

Process actual +

supply

3

not connected

4

Process actual -

Frequency

1

+ 24 V - supply sensor

- internal

2

Clock input +

supply

3

Clock input - (GND)

4

not connected

Frequency

1

not connected

- external

2

Clock input +

supply

3

Clock input -

4

not connected

Pt-100

1

not connected

(see

2

process actual 1(current supply)

Note

3

process actual 3 (GND)

below)

4

process actual 2 (compensation)

2

4

Pt 100

Clock +

Clock -

Clock +

Clock -

3

2

1

+24 V

2

3

3

* With external supply of the sensors, the mass of the standard signal must be

connected to the mass of the supply voltage.

Circular plug

M12

2

4

4 ... 20 mA

GND