MANUAL TUNE - FUNCTIONS

Access to the manual

TUNE functions is obtained by selection X.TUNE in the main menu and briefly

pressing the MANUAL/AUTOMATIC key, or on abortion of countdown, by releasing the MANUAL/
AUTOMATIC key.

The following parameters, which are automatically determined during

X.TUNE, may be manually

present or adjusted afterwards.

TUNE-END

- Return to main menu

TUNE-POS

- Present end position

The

AUTOTUNE function determines the end positions of the control armature from the physically stops.

Certain armatures (e.g. rotating vanes) have no physically stops, so that the end positions must be
manually present using

TUNE-POS. When executed immediately afterwards, AUTOTUNE assumes the

manual end settings and continues with the setting of the positioning system and optimization of the
positioner.

NOTE

If manual presetting of the end positions by means of

TUNE-POS is necessary, it must be

done

before execution of AUTOTUNE.

ATTENTION!

During execution of the

AUTOTUNE function, the valve moves on its own away from its

current position. For this reason, never execute

AUTOTUNE while the process is

running!

release

move to max.

position

move to min.

position

change min. PWM T.V.
for pressurizing valve

change min. PWM T.V. for
venting valve

display of opening time (s)

display of closing time (s)

5 s

(Countdown)

AUTOTUNE

MANUAL TUNE