8630 - 71

O

PERATION

AND

C

ONTROLLER

F

UNCTIONS

Effect of limitation of the opening speed after a step in the setpoint

X.TIME

Limitation of the correcting speed

Factory setting: 1 s

Opening time for full stroke (in seconds)

Closing time for full stroke (in seconds)

If the correcting speed is to be limited, values can be entered for

T:OPN and T.CLS that lie between the

minimum values determined by

X:TUNE and 60 s.

NOTE

When executing the function

X.TUNE, the minimum opening and closing time for T.OPN

and

T.CLS is automatically entered for the full stroke. In this way it is possible to traverse at

maximum speed.

XX

XX

Valve stroke [%]
(POS, CMD)

Setpoint

Actual
value

T.OPN

t

NOTE

If positioning times < 1 s are determined from the

AUTOTUNE, X.TIME is automatically

copied to the main menu and the relevant value is set to 1 s.