Operating voltage (circular plug m 12) – Burkert Type 8630 User Manual

Page 47

Advertising
background image

8630 - 45

I

NSTALLATION

Operating voltage (circular plug M 12)

Pin

Allocation

External connection

1

+ 24 V

2

not connected

3

GND

4

not connected

24 V DC ± 10 %
max. residual ripple 10 %

Pin

Allocation

Signal level

1

Proximity switch 1 + (NO)

2

Proximity switch 1 GND

3

Proximity switch 2 + (NO)

4

Proximity switch 2 GND

open / 24 V

+24 V DC

GND

GND

1

2

S1

open / 24 V

+24 V DC

GND

GND

3

4

S2

Inductive proximity switches (circular socket M 8)

Output signals for SPS (circular plug M16)

Pin

Allocation

External connection/signal level

A

Setpoint GND

B

Setpoint + (0/4..20 mA or 0..5/10 V)

C

Analog position feedback +

D

Analog position feedback GND

E

Binary output 1

F

Binary output 2

G

Binary output GND

H

Binary input +

J

Binary input GND

K

not connected

L

not connected

M

not connected

A

B

+ (0/4 ... 20 mA or 0..5/10 V)
completely isolated electrically

GND

24 V / 0 V

24 V / 0 V

GND

E

F

G

H

J

GND

+

0 ... 5 V

(log. 0)

10 ... 30 V (log. 1)

GND

C

D

+ (0/4 ... 20 mA or 0 ... 5/10 V)
completely isolated electrically