Description of the procedure – Burkert Type 8630 User Manual

Page 57

Advertising
background image

8630 - 55

O

PERATION

AND

C

ONTROLLER

F

UNCTIONS

After the voltage supply has been switched on, the positioner is in the process operating level in the
AUTOMATIC mode. To specify the basic settings, switch to the configuration level. Depress the MANU-
AL/AUTOMATIC key for 5 seconds. The display then shows ACTFUNCT, the first item of the main menu.

To make a setting under the menu item

ACTFUNC, press the MANUAL/AUTOMATIC key briefly.

Then one of the sub-menu items appears on the display. The arrow keys are used to switch between
these sub-items, enabling the desired settings to be made. The desired setting is confirmed after
selection by pressing the MANUAL/AUTOMATIC

key. The arrow keys are also used to switch between

the items of the main menu (

ACTFUNCT, INPUT, ...).

Description of the procedure

- single-acting

- double-acting

NOTE

At the level of the sub-menu items, the selected function is shown by the three or four
characters at the right of the 8-digit display. These characters flash on the display.

ACTFUNC -

Function of actuator

➔ Enter under this menu item the function of the pneumatic actuator used in combination with the TOP

Control. This function is marked on the rating plate of the actuator.

INPUT - Selected standard signal

➔ Enter under this menu item the standard signal used for the setpoint.

- Current 4 ... 20 mA

- Current 0 ... 20 mA

- Voltage 0 ... 10 V

- Voltage 0 ... 5 V

Advertising