Configuration in the profibus dp master, Configuration of the process values – Burkert Type 8630 User Manual

Page 127

Advertising
background image

8630 - 125

P

ROFIBUS

DP

Configuration in the PROFIBUS DP master

User parameters (hex paramaters) are not required.

Configuration of the process values

First the process data input are entered (from the TOP Control Continuous to the control).

PDI

: Process Data Input

(from the TOP Control Continuous to the control)

In the same order as in the selection in the TOP

Control Continuous and only process

data (

PDI) activated in the configuration menu may be entered.

NOTE

Name

Description

Identifiers

PDI:POS

Actual position (Position)
Actual value of positioner in ‰.

Range of values 0 ... 1000.

Values < 0 or > 1000 are possible when e.g.
AUTOTUNE was not run throug properly.

GSD file: PDI:POS

Identifiers (HEX): 41, 40, 00

PDI:CMD

Setpoint position (Command)

Positioner setpoint in ‰. Range of values 0 ... 1000.

GSD file: PDI:CMD

Identifiers (HEX): 41, 40, 01

PDI:PV

Process actual value (Process Value)

Actual value of process controller in physical units

(as set in menu P.CO INP or P.CO SCAL), max.
range of values -999 ... 9999, depending on internal

scaling

GSD file: PDI:PV

Identifiers (HEX): 41, 40, 02

PDI:SP

Process setpoint (Setpoint)

Setpoint of value of process controller in physical units
(as set in menu P.CO INP or P.CO SCAL), max. range
of values -999 ... 9999, depending on internal scaling

GSD file: PDI:SP

Identifiers (HEX): 41, 40, 03

PDI:TEMP

Device temperature (Temperature)

Temperature in 0.1 °C is measured on the CPU board
with a sensor,

range of values -550 (-55 °C) ... +1250 (+125 °C)

GSD file: PDI:TEMP

Identifiers (HEX): 41, 40, 04

PDI:MODE

Operation mode (Operation Mode)
Operation mode:
0: AUTO 10: P.TUNE

1: HAND 12: BUSSAFEPOS

2: XTUNE
3: MENUE
9: P.QLIN

GSD file: PDI:Mode

Identifiers (HEX): 41, 00, 05

PDI:ERR

Error (Error)

States the number of the process value (output) that

was not written. The value is retained until deleted with

PD-O:ERR.
HEX
14 PD-O:CMD
15 PD-O:SP
16 PD-O:MODE

GSD file: PDI:ERR

Identifiers (HEX): 41, 00, 06

Advertising