Start the automatic adaptation of the positioner to the current operating conditions

X.TUNE

- Autotune for positioner

➔ Start the program for automatic parametrization of the TOP Control Continuous via the menu item

X.TUNE.

The following functions are initiated automatically:

Adaptation of the sensor signal to the (physical) stroke of the valve used

Determination of parameters of the PWM signals for driving the solenoid valves integrated in the
TOP Control Continuous.

Setting of the controller parameters of the positioner. Optimization is done according to the
criteria: as short a correcting time as possible and simultaneously freedom from overshoot.

➔ Start AUTOTUNE by calling up X.TUNE in the main menu.
➔ Then depress the MANUAL/AUTOMATIC key for 5 seconds.

ADDFUNCT

See section

Configuring the supplementary functions.

➔ Jump over this menu item on first commissioning.

NOTE

The basic settings onthe TOP Control Continuous are made in the factory. On
commissioning, nevertheless, execution of X.TUNE is

absolutely necessary. TOP Control

Continuous then determines automatically the optimum settings for the current operating
conditions.
If the supplementary function

X.CONTRL is present in the main menu during execution of

X.TUNE, the positioner dead band X.CO DBND is additionally determined automatically as
a function of the frictional behaviour of the positioning mechanism (see chapter
Supplementary Functions - X.CONTROL).

NOTE

To cancel

AUTOTUNE, operate both arrow keys at the same time and select X.TUN BRK .

Display

Description

TUNE 5

Countdown from 5 to 0 start of

AUTOTUNE

TUNE 4

:

TUNE 0

¦ X.T INIT

Display of the autotune phase in progress at the moment

¦ X.T A1-P

(continuation is indicated by a rotating bar to the left of the

¦ X.T TOPN

display)

¦ X.T TCLS

:

TUNE-END

Flashing display

end of

AUTOTUNE

X.ERR X

Message on occurrence of an error

(Indication right: Error number, see chapter

Maintenance

and controller fault rectification)