Process value (circular plug m8, continuation), Termination connection for devicenet systems – Burkert Type 8630 User Manual

Page 140

Advertising
background image

138 - 8630

D

EVICE

N

ET

Input type *

Pin Assignment

Jumper

external circuit

Frequency
internally

supplied

1

2
3
4

+ 24 V supply sensor
clock input +
not assigned
clock input - / GND

Frequency

externally
supplied

1

2
3
4

not assigned

clock input +

not assigned

clock input -

Pt-100 (see
Note)

1

2
3
4

not assigned
process actual 1 (current supply)
process actual 2 (GND)
process actual 3 (compensation)

*

adjustable via software

Process value (circular plug M8, continuation)

For line compensation reasons, connect sensor Pt-100 via three conductors. PIN3 and 4
must be bridged at the sensor.

NOTE

Termination connection for DeviceNet systems

On installing a DeviceNet system, it is important to have the correct termination circuit for the data lines.
The circuit avoids the occurrence of faults through signal reflections on the data lines. For this purpose
the main line is to be terminated at both ends with resistors of respectively 120

Ω and 1 / 4 W power

loss.

Pt100

2

3
4

Actual process value for the fluid flow controller option (2 M8 round
plugs), or optionally: with temperature sensor input (3 M8 round
plugs)

* With external supply of the sensors the mass of the standard

signal must be connected with the mass of supply voltage.

Input type

Plug

Pin

Assignment

Jumper

external circuit

internally

supplied
transmitter*

1

1

2

3 + 4

+ 24 V -

transmitter supply p1

4 ... 20 mA - transmitter output p1

not assigned

2

1

2

3 + 4

+ 24 V - transmitter supply p2
4 ... 20 mA - transmitter output p2
not assigned

option:
temperature
transmitter*

3

1

3

2 + 4

+ 24 V -

transmitter supply

4 ... 20 mA - output
transmitter temperature

not assigned