Burkert Type 8630 User Manual

Page 76

Advertising
background image

74 - 8630

O

PERATION

AND

CONTROLLER

FUNCTIONS

SAFEPOS

Entering the safety position

Factory setting: 0 %

SAFEPOS

SPOS XXX

Enter

safety position (0 ... 100 %)

*

With the fast pressurize / fast vent variant, two valves are driven in each case to obtain faster
pressurizing and venting.

* When the safety position is 0 % or 100 %, the actuator will be fully vented or pressurized as soon as the safety position is
activated int he supplementary function

SIG-ERR or BIN-IN.

The safety position set is only moved to when a corresponding signal is present at the
binary input (for configuration see

BIN-IN), or on occurrence of a signal error (for

configuration see

SIG-ERR).

This function is executed only in the AUTOMATIC mode.

ATTENTION!

Advertising