Safety settings on bus failure

The actuator moves to the position corresponding to the setpoint last transmitted (default setting).
For other setting options (see the chapter

Settings on the TOP Control Continuous)

Drop line length (Drop Lines)

Technical data

EDS file

BUER8630.EDS

Icons

BUER8630.ICO

Baud rate

125 kBit/s, 250 kBit/s, 500 kBit/s (adjustable via keys at the device or via
network);
Factory setting 125 kBit/s

Adress

0 ... 63; (adjustable via keys at the device or via network);
Factory setting 63

Process data

7 static Input Assemblies
(Input: from TOP

Control Continuous to DeviceNet Master/Scanner)

4 static Output Assemblies

Total line length according to DeviceNet specification
(Total line length = sum of all mein and drop lines)

Baud rate

Maximum total line length

Thick Cable

Thin Cable

125 kBaud

500 m

100 m for all baud rates

250 kBaud

250 m

500 kBaud

100 m

Baud rate

Length of drop lines

Maximum length

Maximum total length of drop lines in network

125 kBaud

6 m for all baud rates

156 m

250 kBaud

78 m

500 kBaud

39 m